TMPN(G) series power oil-filled transformers are an important component for ensuring stable power supply in various industries. They convert electrical energy in AC networks, stepping down high voltage to a level suitable for consumption. Three-phase oil-filled transformers of the TMPNG series with natural oil cooling are designed to power oil production electric pumps. They are designed for operation in moderate and cold climates.
Design Features
TMPN(G) series transformers have a well-thought-out design that ensures their reliability and durability in operation. The features of the tank structure and internal components contribute to efficient cooling and protection from external influences; in particular, the hermetic design prevents oil contact with air.
- The tanks of hermetic TMPNG transformers can be rectangular with corrugated walls or with radiators.
- On the tank lid, there is a tap or plug for filling oil, and at the bottom of the tank – a plug for draining oil and a tap or plug for taking a sample.
- For controlling the oil level, a float-type oil indicator is installed on the tank lid of transformers with corrugated tanks, and on the tank wall of transformers with radiator tanks.
- A thermometer is installed in the tank to measure the temperature of the upper oil layers.
- The oil in hermetic TMPNG type transformers does not come into contact with air and does not oxidize.
- The transformer design includes a cable entry and voltage output for reliable cable connection.
- The HV and LV bushings are protected by a box and installed on the side wall, protection degree IP-13.
- The magnetic cores of the transformers are laminated core type with a multi-step cross-section shape of cores and yokes.
- The core limbs are pressed using fiberglass banding tape.
- Using the “Step-Lap” stacking scheme during steel cutting ensures reduced no-load losses.
Technical Specifications of TMPN(G) Transformers
Parameters of TMPN(G) type transformers with corrugated tanks with capacity from 63 to 1000 kV*A. (Below are the characteristics of several TMPN(G) transformers we manufacture, for more details on the types of this series and their characteristics, see the PDF file below)
|
Transformer Type
|
LV Voltage, V
|
Connection Scheme & Group
|
Number of Regulation Steps
|
HV Voltage, V (Current, A) Regulation Steps.
|
No-load losses, kW.
|
Short-circuit losses, kW.
|
Overall Dimensions, mm. |
Oil Mass, kg.
|
Mass, kg.
|
||
| L | B | H | |||||||||
| TMPNG-63/3 | 380 | Yn/Yn-0 | 25 | 1143(31,9)-1110(32,8)-1080(33,7)- 1050(34,6)-1019(35,7)-995(36,6)- 965(37,7)-921(39,49)-905(40,2)- 875(40,2)-850(40,2)-820(40,2)- 790(40,2)-760(40,2)-730(40,2)- 706(40,2)-676(40,2)-645(40,2)- 615(40,2)-585(40,2)-561(40,2)- 531(40,2)-501(40,2)-470(40,2)- 440(40,2) |
0,27 | 1,7 | 1200 | 995 | 1200 | 140 | 650 |
| TMPNG-100/3 | 380 | Yn/Yn-0 | 25 | 2400(24,5)-2325(25,3)-2255(26,1)- 2180(27,0)-2105(28,0)-2030(29,0)- 1955(30,1)-1885(31,2)-1815(32,4)- 1740(33,8)-1660(35,5)-1590(37,0)- 1515(38,9)-1445(40,0)-1370(43,0)- 1300(45,5)-1220(45,5)-1145(45,5)- 1075(45,5)-995(45,5)-925(45,5)- 855(45,5)-780(45,5)-705(45,5)- 626(45,5) |
0,29 | 1,97 | 1200 | 995 | 1050 | 180 | 690 |
| TMPNG-100/3 | 380 | Yn/Yn-0 | 25 | 1690(34,2)-1646(35,1)-1602(36)- 1558(37,1)- 1514(38.3)-1470(39,3)- 1426(40,5)-1382(41,8)-1338(43,2)- 1294(44,6)-1250(46,2)-1206(46,2)- 1162(46,2)-1118(46,2)-1074(46,2)- 1030(46,2)-986(46,2)-942(46,2)- 898(46,2)-854(46,2)-810(46,2)- 766(46,2)-722(46,2)-678(46,2)- 630(46,2) |
0,29 | 1,97 | 1200 | 995 | 1050 | 180 | 690 |
| TMPNG-100/3 | 380 | Yn/Yn-0 | 25 | 2237(27)-2170(27)-2102(28)- 2035(29)- 1967(29)-1925(29)- 1858(29)-1790(29)-1722(29)- 1655(29)-1613(36)-1545(36)- 1478(36)-1410(36)-1343(36)- 1258(36)-1190(40)-1123(49)- 1055(49)-988(49)-903(49)-836(49)- 768(49)-701(49)-633(49) | 0,29 | 1,97 | 1200 | 995 | 1050 | 180 | 690 |
| TMPNG-100/3 | 380 | Yn/Yn-0 | 15 | 1613(36)-1545(36)-1478(36)- 1410(36)- 1343(36)-1258(36)- 1190(40)- 1123(49)- 1055(49)- 988(49)-903(49)-836(49)-768(49)- 701(49)-633(49) | 0,29 | 1,6 | 1145 | 995 | 1050 | 180 | 690 |
| TMPNG-100/3 | 380 | Yn/Yn-0 | 5 | 1270(45,4)-1358(42,5)-1443(40)- 1527(38)-1610(36) | 0,3 | 1,97 | 1200 | 910 | 1000 | 160 | 690 |

Dimensions
Advantages of Using TMG Transformers
Using TMPN(G) series transformers offers a number of significant advantages, making them an efficient and reliable solution for power supply systems. These advantages are due to the special design and production technologies aimed at increasing operational characteristics and extending the service life of the equipment.
- Transformers do not require additional costs during commissioning.
- They do not require preventative maintenance and overhauls throughout their service life.
- The hermetic tank design prevents oil contact with air, which eliminates its oxidation.
- Using the “Step-Lap” magnetic core stacking scheme ensures reduced no-load losses.
- Structural elements contribute to reducing additional losses.
- The reliable design of the cable entry and voltage output ensures safe connection.
Areas of Application
TMPN(G) series transformers are widely used in various industries where reliable and efficient electrical energy conversion is required. Their design features and technical characteristics make them suitable for both specific industrial needs and general power distribution systems.
- Energy Sector: used in power distribution systems and at transformer substations.
- Industry: applied in industrial enterprises, including heavy industry, manufacturing facilities, chemical plants, and mining enterprises.
- Oil and Gas Industry: specialized application for powering oil production electric pumps.
- Infrastructure: used in large infrastructure facilities such as shopping centers, airports, and hospitals.
- Renewable Energy: integrated into wind and solar power plant systems.
- Agriculture: can be used for the needs of agricultural facilities.
- Transport: used in railway infrastructure and other transport systems.
- Housing and Communal Sector: used in urban and rural electrical networks for power supply to consumers.
Compliance with Standards
TMPN(G) series transformers are manufactured in compliance with rigorous national and international quality and safety standards. This confirms their reliability, efficiency, and compliance with modern requirements for electrical equipment, ensuring confidence in their use.
- Transformers comply with IEC-60076 standards.
- Comply with GOST R 52719-2007.
- Comply with TU U31.1-00213440-015:2006.
- Production is certified according to ISO 9001:2008.
To obtain precise characteristics of TMPN(G) transformers or to place an order, please contact the official representative of LLC “Ukrelectroapparat” or write to the email address zakaz@uea.km.ua.